Valve technology
For constant control of the flow temperature with protection against condensation in high-efficiency boilers connected to buffer tanks (precise top-loading) and to prevent the buffer tank’s hot zone from cooling down during pump run-down
BAFA funding opportunity for heating system optimization through hydraulic balancing and the installation of flow control technologyThermostatic flow temperature controller with adjustable flow temperature
For constant regulation of the flow temperature with protection against condensation in high-efficiency boilers connected to buffer tanks (precise top-loading) and prevention of the buffer tank’s hot zone from cooling down during pump run-on
Consisting of:
1) Three-way mixing valve, red brass, EPDM seal
G1½ flat-seal, Z-dimensions: L 98 mm × W 49 mm
DN32, DpN 100 mbar, Kvs = 6.4, V'max[100 mbar] = 2.0 m³/h, Q'max = 47 kW [20 K] = 19 L/min [10/45°C]PN 10 bar, Tmax 120°C (Part No. 996 019)2) Thermostat head with immersion sensor, setpoint range 60°C to 90°CCapillary tube length 2 m, immersion probe length 125 mm, Ø 11 mmResponse time approx. 60 sPN 10 bar, Tmax 100°C (Part No. 996 014)3) Immersion sleeve with screw-in nipple R½×186 mm, brass (Part No. 996 015)4) Connection fittings:a) 2x compression fitting with union nut, flat seal, DN32, G1½×Ø35 (Part No. 996 043)b) Screw nipple insert, flat-sealing, R1¼×DN32 (for G1½ union nut) (Part No. 996 033)5) Black T-fitting, TsF 1¼x1¼x½ (Part No. 996 057)6) Double nipple, black, NDs 1¼x1¼ (replacement part no. 996 066)
DN32, DpN 100mbar, Kvs = 6.4, V'max[100mbar] = 2.0m³/h, Q'max = 47kW [20K] = 19l/min [10/45°C]