Valve technology
For constant control of the flow temperature with protection against condensation in high-efficiency boilers connected to buffer tanks (precise top-loading) and to prevent the buffer tank’s hot zone from cooling down during pump run-down
BAFA funding opportunity for heating system optimization through hydraulic balancing and the installation of flow control technologyThermostatic flow temperature controller with adjustable flow temperature
For constant regulation of the flow temperature with protection against condensation in high-efficiency boilers connected to buffer tanks (precise top-loading) and prevention of the buffer tank’s hot zone from cooling down during pump run-on
Consisting of:
1) Three-way mixing valve, red brass, EPDM seal
G1 flat-seal, Z dimensions: L 71.0 mm × W 35.5 mm
DN20, DpN 100 mbar, Kvs = 3.5, V'max[100 mbar] = 1.1 m³/h, Q'max = 26 kW [20 K] = 11 L/min [10/45°C]PN 10 bar, Tmax 120°C (Part No. 996 017)2) Thermostat head with immersion sensor, setpoint range 60°C to 90°CCapillary tube length 2 m, immersion probe length 125 mm, Ø 11 mmResponse time approx. 60 sPN 10 bar, Tmax 100°C (Part No. 996 014)3) Immersion sleeve with screw-in nipple R½×186 mm, brass (Part No. 996 015)4) Connection fittings:a) 2x compression fittings with union nuts, flat-seal type, DN20, G1ר22 (Part No. 996 041)b) Screw nipple insert, flat-seal type, R¾×DN20 (for G1 union nut) (Part No. 996 031)5) Black T-fitting, TsF ¾x¾x½ (Part No. 996 055)6) Double nipple, black, NDs R¾x¾ (replacement part no. 996 064)
DN20, DpN 100mbar, Kvs = 3.5, V'max[100mbar] = 1.1m³/h, Q'max = 26kW [20K] = 11l/min [10/45°C]