Valve technology
For automatic, hydraulic balancing of downstream condensing flue gas heat exchangers of boilers and CHP units, especially in conjunction with our rMIX 250 3×3 C loading station.
BAFA funding opportunity for heating system optimization through hydraulic balancing and the installation of flow control technology
Thermostatic flow temperature limiter with adjustable minimum temperature
For automatic hydraulic balancing of downstream condensing flue gas heat exchangers from boilers and CHP units, particularly in combination with our rMIX 250 3×3 C loading station.
Consisting of:
1) Actively opening valve body with fixed minimum flow rate DN32
Kvs = 12.5
V'max [100 mbar] = 4.0 m³/h
Q'max = 92 kW [20 K]
Male thread, PN 8 bar, Tmax 200°C
2) Thermostat head with immersion sensor
Setpoint range 25°C to 70°C
Capillary tube length 2 m, capillary tube seal: compression fitting R¾<br/>Sensor dimensions: 16 × 210 mm<br/>3) Immersion sleeve HSF R¾ × 220 mm<br/>4) 2x screw nipple insert, flat-sealing, R1¼<br/>5) Black T-fitting, TsF 1¼x1¼x¾
Kvs = 12.5
V'max [100 mbar] = 4.0 m³/h
Q'max = 92 kW [20 K]