Valve technology
For automatic, hydraulic balancing of downstream condensing flue gas heat exchangers of boilers and CHP units, especially in conjunction with our rMIX DN25 3×3 C loading station.
Specialist partner access required
BAFA funding opportunity for heating system optimization through hydraulic balancing and the installation of flow control technology
Thermostatic flow temperature limiter with adjustable minimum temperature and a fixed minimum flow rate of approx. 1%
For automatic hydraulic balancing of downstream condensing flue gas heat exchangers from boilers and CHP units, particularly in combination with our rMIX DN25 3×3 C loading station.
Consisting of:
1) Actively opening valve body VUO DN20 with fixed minimum flow rate DN20
Kvs = 3.2
V'max [60 mbar] = 0.8 m³/h<br/>Q'max = 19 kW [20 K]<br/>EPDM seal, inlet nipple R¾×Rp¾, outlet socket <br/>Conical threaded connection G1 PN 10 bar on the inlet side, Tmax 120°C (Part No. 996 004)<br/>2) Thermostat head with TK-WTF spiral immersion sensor
Setpoint range 20°C to 70°C
Capillary tube length 2 m, capillary tube seal: R½ compression fitting
Spiral immersion sensor length 125 mm, response time approx. 5 s<br/>CAUTION: Immersion sensor comes into contact with heating water—provide a shut-off valve on site!
PN 10 bar, Tmax 90°C (Part No. 996 005)
3) Black T-fitting, TsF ¾x¾x½ (Part No. 996 055)
Kvs = 3.2
V'max [60 mbar] = 0.8 m³/h
Q'max = 19 kW [20 K]