Valve technology
For automatic hydronic balancing of individual heat exchangers such as domestic hot water storage tanks, air heaters, swimming pool heat exchangers and ventilation and air conditioning systems.
BAFA funding opportunity for heating system optimization through hydraulic balancing and the installation of separate control technology
Thermostatic return temperature limiter with adjustable maximum temperature and a fixed minimum flow rate of approximately 1%
For automatic hydraulic balancing of individual heat exchangers such as domestic hot water storage tanks, air heaters, swimming pool heat exchangers, and HVAC systems.
Consisting of:
1) Actively closing valve body VUS DN32 with a fixed minimum flow rate of approx. 1%
DN32, DpN 100 mbar, V'maxN 3.95 m³/h, Kvs 12.5, straight-through design, red brass
Male thread, PN 8 bar, Tmax 200°C<br/>2) Thermostat head with immersion sensor <br/>Setpoint range 25°C to 70°C<br/>Capillary tube length 2 m, capillary tube seal: R¾ compression fitting<br/>Sensor dimensions: 16 × 210 mm<br/>3) HSF immersion sleeve R¾ × 220 mm<br/>4) 2x screw nipple inserts, flat-sealing, R1¼
DN32, DpN 100mbar, V'maxN 3.95m³/h, Kvs 12.5, straight through, red cast iron