Valve technology
For automatic hydronic balancing of individual heat exchangers such as domestic hot water storage tanks, air heaters, swimming pool heat exchangers and ventilation and air conditioning systems.
BAFA funding opportunity for heating system optimization through hydraulic balancing and the installation of flow control technology
Thermostatic return temperature limiter with adjustable maximum temperature and a fixed minimum flow rate of approximately 1%
For automatic hydraulic balancing of individual heat exchangers such as domestic hot water storage tanks, air heaters, swimming pool heat exchangers, and ventilation and air conditioning (VAC) systems.
Consisting of:
1) Actively closing valve body VUS DN25 with a fixed minimum flow rate of approx. 1%<br/>DN25, DpN 100 mbar, V'maxN 1.9 m³/h, Kvs 5.7, straight-through design, nickel-plated red brass<br/>Inlet socket Rp1, outlet threaded connection, conical G1¼(i) × R1<br/>PN 10 bar, Tmax 120°C, (Part No. 996 011)<br/>2) Thermostat head with helical immersion sensor TK-WTF<br/>Setpoint range 20°C to 70°C<br/>Capillary tube length 2 m, capillary tube seal: R½ compression fitting<br/>Spiral immersion sensor length: 125 mm, response time: approx. 5 s<br/>CAUTION: The immersion sensor comes into contact with the heating water—provide a shut-off valve on site!<br/>PN 10 bar, Tmax 90°C (Part No. 996 005)<br/>3) Black T-fitting, TsF 1x1x½ (Part No. 996 056)<br/>4) Black double nipple, NDs 1x1 (replacement part no. 996 065)
DN25, DpN 100mbar, V'maxN 1.9 m³/h, Kvs 5.7 straight through, nickel-plated gunmetal