Two-zone loading
For highly efficient two-zone loading of a buffer cylinder by a heat generator with return temperature increase as a mixing circuit
Specialist partner access required
Specialist partner access required
Specialist partner access required
BAFA Funding Opportunity for Heating System Optimization Through Hydraulic Balancing and Installation of Separate Control TechnologyrendeMIX Multi-Port Mixing Manifold with 3/3-Way Tangential Mixing Valve DN25×G1½(a) MsGuss (green adapter), valve and cover Ms58For highly efficient two-zone charging of a buffer tank by a heat generator with return temperature increase as a mixing circuitActuator EMS 240, 230 V AC, 50 Hz, 3.5 VA, 3-point signal, 5 Nm (240 h), 240°, 93sReturn temperature boost mixing unit with 2 connections to the heat generator and 3 connections to the buffer tank, Cu Ø35×1, DN32×G1½(a) flat, pipe spacing 100 mm1 integrated gravity brake/backflow preventer, Dp 10 mbarGenerator circuit (HT-RLA): Kvs = 6.2 × V'max[250 mbar] = 3.1 m³/h × Q'max[20 K] = 72 kW × Q'max[10K] = 36 kW × Leak rate < 0.1%5 thermometers 0–120°C, Ø63 mm, solder sleeves Ms585 ball valve fittings, straight-through DN25, PN32, G1½(i)×Rp1 flat-seal, stuffing box, sealing hole, stem with aluminum wing handle
EPP insulation mold, 40 g/l, black, 300×450 mm, Quick-installation kitWith pump flange G1½(i) for DN25 pump on the mixed heat generator return (5)Assembly does NOT include a pump compensator – PAS L180 (Part No.: 001 338)Assembly does not include a pumpModel DN 25 – lightweight version, PN 10 bar, Tmax 120°C
Generator circuit (HT-RLA): Kvs = 6.2 • V'max[250mbar] = 3.1m³/h • Q'max[20K] = 72kW • Q'max[10K] = 36kW • Leakage rate < 0.1%