rMIX DN25 2x3 LR 5

Item number: 001 334

Two-zone loading

For highly efficient two-zone loading of a buffer cylinder by a heat generator with return temperature increase as a mixing circuit

Gross price €9,999.00
Your price
€9,999.00 plus VAT.
Delivery time depends on the recipient country

Recommended accessories

Product documentation

Assembly instructions

Assembly instructions for motors

Spare parts drawing

Tender text

BAFA funding opportunity for heating system optimization through hydraulic balancing and the installation of separate control technology<br/>rendeMIX multi-port mixing manifold with 3/3-way tangential mixing valve DN25×G1½(a) MsGuss (red adapter), valve and cover Ms58<br/>For highly efficient two-zone charging of a buffer tank by a heat generator with return temperature increase as a mixing circuit<br/>EMS 240 actuator, 230 V AC, 50 Hz, 3.5 VA, 3-point signal, 5 Nm (240 h), 240°, 93s<br/>Return temperature boost mixing unit with 2 connections to the heat generator and 3 connections to the buffer tank, CuØ35×1, DN32×G1½(a) flat, pipe spacing 100 mm<br/>1 integrated gravity brake/backflow preventer, Dp 10 mbar<br/>Generator circuit (HT-RLA): Kvs = 6.2 × V'max[250 mbar] = 3.1 m³/h × Q'max[20 K] = 72 kW × Q'max[10K] = 36 kW × Leak rate < 0.1%<br/>5 thermometers 0–120°C, Ø63 mm, solder sleeves Ms58<br/>5 ball valve fittings, straight-through DN25, PN32, G1½(i)×Rp1 flat-seal, stuffing box, sealing hole, stem with aluminum wing handle

EPP insulation mold, 40 g/l, black, 300×450 mm, Quick-installation kit<br/>With pump flange G1½(i) for DN25 pump on the mixed heat generator return (5)<br/>Assembly does NOT include a pump compensator – PAS L180 (Part No.: 001 338)<br/>Assembly does not include a pump<br/>Model DN 25 – lightweight version, PN 10 bar, Tmax 120°C

Performance data

Generator circuit (HT-RLA): Kvs = 6.2 • V'max[250mbar] = 3.1m³/h • Q'max[20K] = 72kW • Q'max[10K] = 36kW • Leakage rate < 0.1%