Product search
RTV DN40s T45-65 Feed set
Configure product variant
Performance class
V'max[100mbar] = 4.0m³/h
Q'max = 92kW [20K] = 38l/min [10/45°C]
Product documentation
Tender text
Baunach article master data Version: 19.11.24
BAFA funding opportunity within the scope of heating system optimisation through hydraulic balancing and installation of technology for volume flow control
Return temperature distributor DN40 45-65°C
For optimal feeding at buffer storage tanks in two zones of sources with fluctuating temperatures such as solar or fresh water modules.
Thermostatic return temperature distribution valve with adjustable distribution temperature 45-65°C.
Consisting of:
1) Three-way distribution valve, gunmetal, EPDM seal
DN40, DpN 250mbar, V'maxN 6.3m³/h, Kvs 12.5
PN 10bar, Tmax 120°C
Leads the return from input I below the set temperature to the straight output II (marked blue) and above the set temperature to the angled output III (marked red).
2) Connection fittings:
3x screw nipple insert, flat sealing, R1½
3) Thermostatic head Tension with rod sensor, setpoint range 45°C to 65°C, capillary tube length 2m
Capillary tube seal compression fitting R½, sensor length/diameter 170mm/10mm
Reaction time approx. 5s, PN 10bar, Tmax 90°C
4) Immersion sleeve G 1/2 PN 40 copper Immersion length 185 mm
5) Sensor connection
T-piece black for sensor Rp1½x1½x½
Performance data
DN40, DpN 250mbar, V'maxN 6.3m³/h, Kvs 12.5