Product search
rMIX DN25s 3x3C VR 6
Accessories needed
|
VTB DN32s T25-70 Condenser Set996106 |
|
VTB DN40s T25-70 Condenser Set996107 |
|
VTB DN50s T25-70 Condenser Set996108 |
Recommended accessories
REG-FWR996020 |
Schl KuH DN32-50 set996167 |
ISO KuH DN32 G1½(i)xRp1¼996086 |
Configure product variant
Nominal width
Performance class
Kvs = 11.6 V'max[250mbar] = 5.8m³/h
Q'max[20K] = 135kW
Condenser circuit (LT):
Kvs = 9.2 V'max[250mbar] = 4.6m³/h
Q'max[10K] = 53kW
Flow direction producer
Pump flange
Product documentation
Assembly instructions
Assembly instructions: For specialist partners only.
Please log in here or register here
Actuator multi-way mixer: For specialist partners only.
Please log in here or register here
Spare parts drawing
Spare parts drawing For specialist partners only.
Please log in here or register here
Data sheet
GAEB
Tender text
Baunach article master data Version: 10.05.24
BAFA funding opportunity as part of heating system optimisation through hydraulic balancing and installation of separate control technology
rendeMIX multi-port mixing manifold with 3/3-way tangential mixing valve DN25×G1½(a) MsGuss (adapter green), plug and cover Ms58
For highly efficient two-zone charging of a buffer tank by a heat generator with return temperature increase and separate flue gas condenser or two return connections (three-chamber manifold).
Actuator EMS 240, 230V~ 50Hz 3.5VA 3-point signal, 5Nm (240h), 240°, 93s
Mixer assembly with 3 connections to the heat source and separate charging circuit output, CuØ35×1, pipe spacing 100mm, DN32×G1½(a) flat
1 integrated backflow preventer, Dp10mbar and 1 external flow differential pressure regulator, Dp80mbar mounted on the mixing circuit flow (5) in Ms58 adapter L 90mm
Generator circuit (HT-RLA): Kvs = 11.6 V'max[250mbar] = 5.8m³/h Q'max[10K] = 135kW Leakage rate < 0.1% - Condenser circuit (NT): Kvs = 9.2 V'max[250mbar] = 4.6m³/h Q'max[20K] = 107kW
6 Thermometers 0-120°C, Ø63mm, soldering sleeves Ms58
6 ball valve screw connections, DN32 passage, PN25, G1½(i)×Rp1¼ flat-sealing, stuffing box, spindle with square drive SW25
Insulating moulded tray EPP 40g/l, black, 300×450mm, quick assembly kit
With pump flange G1½(i) for pump DN25 on heat generator flow (6)
Assembly includes ONE pump balancing piece PAS L180 (part no.: 001 338) and ONE pump balancing piece PAS L90 (part no.: 001 347) - both with screwed connections G1½(a)×G1½(i) for balancing a pump DN25, length 180mm/90mm, insulated.
Assembly does not contain a pump
Model DN 25 - manifold assembly for manifold connection from RIGHT, PN 10bar, Tmax 120°C
ATTENTION: CANNOT BE USED WITHOUT FLOW TEMPERATURE LIMITER (VTB) THERMOSTATIC VALVE! Available in DN32s (part no. 996 106), DN40s (part no. 996 107) or DN50s (part no. 996 108).
Performance data
Generator circuit (HT-RLA): Kvs = 11.6 V'max[250mbar] = 5.8m³/h Q'max[10K] = 135kW Leakage rate < 0.1% - Condenser circuit (NT): Kvs = 9.2 V'max[250mbar] = 4.6m³/h Q'max[20K] = 107kW