Product search
VTB DN50s T25-70 Condenser Set
Configure product variant
Performance class
V'max[100mbar] = 6.3m³/h
Q'max = 150kW [20K]
Product documentation
Tender text
Baunach article master data Version: 19.11.24
BAFA funding opportunity within the scope of heating system optimisation through hydraulic balancing and installation of technology for volume flow control
Thermostatic flow temperature limiter with adjustable minimum temperature
For automatic, hydraulic balancing of downstream condensing exhaust gas heat exchangers of boilers and CHP units, especially in conjunction with our rMIX 250 3×3 C loading station.
consisting of:
1) Valve body active opening with fixed minimum flow DN50
Kvs = 20
V'max [100mbar] = 6.3m³/h
Q'max = 150kW [20K]
External thread, PN 8bar, Tmax 200°C
2) Thermostatic head with immersion sensor
Setpoint range 25°C to 70°C
Capillary tube length 2m, capillary tube seal compression fitting R¾
Sensor dimension 16x210mm
3) Immersion sleeve HSF R¾×220mm
4) 2x screw nipple insert, flat sealing, R2
5) T-piece black, TsF 2x2x¾
Performance data
Kvs = 20
V'max [100mbar] = 6.3m³/h
Q'max = 150kW [20K]