WLFbox DN25s 3x3 VR 1

Item no. 001 373 Manifold products
For highly efficient two-zone charging of a buffer tank with priority hot water preparation by a heat generator with minimum temperature release and water quantity balancing (hydraulic separator) via NT circuit of the buffer tank to the three-chamber manifold.

Recommended accessories

								

Schl KuH DN32-50 set

996167
								

ISO KuH DN32 G1½(i)xRp1¼

996086

Further information?

Further questions?

Contact technical support
					

Configure product variant

Nominal width

DN25s

Performance class

Producer circuit (HT):
Kvs = 13.6 • V'max[250mbar] = 6.8m³/h
Q'max[20K] = 158kW • Q'max[10K] = 79kW

Flow direction producer

Flow direction Producer Right

Pump flange

on the heat generator flow (1)

Product documentation

Actuator three-way mixer: For specialist partners only.
Please log in here or register here

Spare parts drawing

Spare parts drawing For specialist partners only.
Please log in here or register here

Data sheet

001373_DBL_2021-04-01.pdf

GAEB

001373.D81

Tender text

Baunach article master data Version: 10.05.24

BAFA funding opportunity as part of heating system optimisation through hydraulic balancing and installation of separate control technology

rendeMIX changeover valve with a 3-way changeover valve DN32×G1½(a) Ms58, plug and cover Ms58

For highly efficient two-zone charging of a buffer tank with priority hot water preparation by a heat generator with minimum temperature release and water quantity balancing (hydraulic separator) via NT circuit of the buffer tank to the three-chamber manifold.

Actuator EMS 90-2P, 230V~ 50Hz 2.3VA 2-point signal, 6Nm (240h), 90°, 60s, closing left, grey adapter

Umschaltbaugruppe mit 3 Anschlüssen zum Verteiler und 3 Anschlüssen zum Pufferspeicher, CuØ35×1, Rohrabstand zum Verteiler 100mm, Rohrabstand zum Pufferspeicher 100mm, DN32×G1½(a) flach

1 integrated backflow preventer, Dp10mbar and 1 integrated return differential pressure regulator, Dp50-70mbar

Generator circuit (HT): Kvs = 13.6 - V'max[250mbar] = 6.8m³/h - Q'max[20K] = 158kW - Q'max[10K] = 79kW - Leakage rate < 0,1%

5 Thermometers 0-120°C, Ø63mm, soldering sleeves Ms58

6 ball valve screw connections, DN32 passage, PN25, G1½(i)×Rp1¼ flat-sealing, stuffing box, spindle with square drive SW25

Insulating moulded tray EPP 40g/l, black, 300×450mm, quick assembly kit

With pump flange G1½(i) for pump DN25 at the heat generator flow of the manifold (1)

Assembly includes TWO pump balancers - PAS L180 - with G1½(a)×G1½(i) fittings for balancing a pump DN25, length 180mm, insulated (part no.: 001 338).

Assembly does not contain a pump

Model DN 25 - manifold assembly for manifold connection from RIGHT, PN 10bar, Tmax 120°C

Performance data

Generator circuit (HT): Kvs = 13.6 - V'max[250mbar] = 6.8m³/h - Q'max[20K] = 158kW - Q'max[10K] = 79kW - Leakage rate < 0,1%

Baunach