Product search
WLFbox DN25s 3x3 VL 1
Recommended accessories
Schl KuH DN32-50 set996167 |
ISO KuH DN32 G1½(i)xRp1¼996086 |
Configure product variant
Nominal width
Performance class
Kvs = 13.6 V'max[250mbar] = 6.8m³/h
Q'max[20K] = 158kW Q'max[10K] = 79kW
Flow direction producer
Pump flange
Product documentation
Actuator three-way mixer: For specialist partners only.
Please log in here or register here
Spare parts drawing
Spare parts drawing For specialist partners only.
Please log in here or register here
Data sheet
Tender text
Baunach article master data Version: 10.05.24
BAFA funding opportunity as part of heating system optimisation through hydraulic balancing and installation of separate control technology
rendeMIX changeover valve with a 3-way changeover valve DN32×G1½(a) Ms58, plug and cover Ms58
For highly efficient two-zone charging of a buffer tank with priority hot water preparation by a heat generator with minimum temperature release and water quantity balancing (hydraulic separator) via NT circuit of the buffer tank to the three-chamber manifold.
Actuator EMS 90-2P, 230V~ 50Hz 2.3VA 2-point signal, 6Nm (240h), 90°, 60s, right-hand closing, grey adapter
Umschaltbaugruppe mit 3 Anschlüssen zum Verteiler und 3 Anschlüssen zum Pufferspeicher, CuØ35×1, Rohrabstand zum Verteiler 100mm, Rohrabstand zum Pufferspeicher 100mm, DN32×G1½(a) flach
1 integrated backflow preventer, Dp10mbar and 1 integrated return differential pressure regulator, Dp50-70mbar
Generator circuit (HT): Kvs = 13.6 - V'max[250mbar] = 6.8m³/h - Q'max[20K] = 158kW - Q'max[10K] = 79kW - Leakage rate < 0,1%
5 Thermometers 0-120°C, Ø63mm, soldering sleeves Ms58
6 ball valve screw connections, DN32 passage, PN25, G1½(i)×Rp1¼ flat-sealing, stuffing box, spindle with square drive SW25
Insulating moulded tray EPP 40g/l, black, 300×450mm, quick assembly kit
With pump flange G1½(i) for pump DN25 at the heat generator flow of the manifold (1)
Assembly includes TWO pump balancers - PAS L180 - with G1½(a)×G1½(i) fittings for balancing a pump DN25, length 180mm, insulated (part no.: 001 338).
Assembly does not contain a pump
Model DN 25 - manifold assembly for manifold connection from LEFT, PN 10bar, Tmax 120°C
Performance data
Generator circuit (HT): Kvs = 13.6 - V'max[250mbar] = 6.8m³/h - Q'max[20K] = 158kW - Q'max[10K] = 79kW - Leakage rate < 0,1%