Two-zone discharge
For highly efficient two-zone discharging of a buffer cylinder in a mixed low-temperature circuit (2nd mixing circuit) with highly efficient use of the return flow of a mixed high-temperature circuit (1st mixing circuit)
Specialist partner access required
Specialist partner access required
Specialist partner access required
Specialist partner access required
BAFA Funding Opportunity for Heating System Optimization Through Hydraulic Balancing and Installation of Separate Control Technology<br/>rendeMIX Multi-Port Mixing Manifold with 3/3-Way Tangential Mixing Valve DN25×G1½(a) MsGuss (green adapter) and 3-way mixing valve DN32×G1½(a) Ms58, valve body and cover Ms58
For highly efficient two-zone discharge of a buffer tank in a mixed low-temperature circuit (2nd mixing circuit) with highly efficient utilization of the return flow from a mixed high-temperature circuit (1st mixing circuit)
1. Mixing circuit: Actuator EMS 90-3P, 230V~ 50Hz 3.5VA 3-point signal, 5Nm (240h), 90°, 70s, gray adapter. 2nd mixing circuit: EMS 240 actuator, 230 V~ 50 Hz, 3.5 VA, 3-point signal, 5 Nm (240 h), 240°, 93s<br/>Dual-circuit manifold assembly with 3 connections to the heat generator (buffer tank or boiler with flue gas heat exchanger), Cu Ø35×1, pipe spacing 100 mm, DN32×G1½(a) flat<br/>3 integrated gravity brakes/backflow preventers, Dp 10 mbar<br/>1st mixing circuit (HT): Kvs = 13.3 × V'max[100 mbar] = 4.2 m³/h • Q'max[20 K] = 98 kW • Leak rate < 0.1% - 2nd mixing circuit (NT): Kvs = 12.9 • V'max[100 mbar] = 4.1 m³/h • Q'max[10 K] = 48 kW • Leak rate < 0.1%<br/>7 thermometers 0–120°C, Ø63 mm, solder sleeves Ms58<br/>7 ball valve fittings, straight-through DN25s, PN20, G1½(i)×Rp1 flat-seal, stuffing box, stem with nylon T-handle<br/>EPP insulation mold, 40 g/l, black, 450×450 mm, Quick-installation kit<br/>With G1½(i) pump flanges for DN25 pumps on the 1st mixed high-temperature (3) and 2nd mixed low-temperature circuit supply lines (5)
Assembly includes TWO pump compensators—PAS L180—with G1½(a)×G1½(i) screw connections for compensating a DN25 pump, length 180 mm, insulated (Part No.: 001 338)<br/>Assembly does not include a pump<br/>Model DN 25 – heavy-duty version, PN 10 bar, Tmax 120°C
1st mixing circuit (HT): Kvs = 13.3 • V'max[100mbar] = 4.2m³/h • Q'max[20K] = 98kW • leakage rate < 0.1% - 2nd mixing circuit (NT): Kvs = 12.9 • V'max[100mbar] = 4.1m³/h • Q'max[10K] = 48kW • leakage rate < 0.1%