Product search
ETR +1 230 3P
Further questions?
Contact technical supportConfigure product variant
Product documentation
Assembly instructions
Assembly instructions: For specialist partners only.
Please log in here or register here
Data sheet
996109_MAL_ETR+1-230-3P_2019-08-07.pdf
GAEB
Tender text
Baunach article master data Version: 19.11.24
BAFA funding opportunity as part of heating system optimisation through hydraulic balancing and installation of separate control technology
Isolating relay +1
For connecting ONE ADDITIONAL servomotor to a controller output with 230V~ 3-point signal. Several cut-off relays can be connected in series - and thus one additional actuator each can be connected to the controller signal.
Terminals U1: WITHOUT USE
Terminals U2: Through signals from the controller or to the first motor (230V~) OPEN/CLOSED L N
Terminals U3: Signals to the additional motor (230V~) OPEN/CLOSED N
Terminals U4: Through signals from the controller or to the first motor (230V~) OPEN/CLOSED L N
Terminals PE: potential earth (NOT required for rendeMIX actuator motors - protection class II)
Load on relay contacts: max. 250V~, max. 3A
Fuse protection power supply: max. 6A
Relay current consumption: 10mA
Working temperature: -10..+50°C, Storage temperature: -30..+80°C
DANGER OF LIFE: Operation only permitted in protective insulated housing 85×85×40mm!