Product search

RTB DN32s T25-70 Adjustment Set
Configure product variant
Performance class
V'max[100mbar] = 4.0m³/h
Q'max = 92kW [20K] = 38l/min [10/45°C]
Product documentation
Tender text
Baunach article master data Version: 19.11.24
BAFA funding opportunity as part of heating system optimisation through hydraulic balancing and installation of separate control technology
Thermostatic return temperature limiter with adjustable maximum temperature, with approx. 1% fixed minimum flow rate
For automatic hydraulic balancing of individual heat exchangers such as domestic hot water storage tanks, air heaters, swimming pool heat exchangers and ventilation and air conditioning systems.
consisting of:
1) Valve lower section actively closing VUS D 320 with approx. 1% fixed minimum flow rate
DN32, DpN 100mbar, V'maxN 3,95m³/h, Kvs 12,5, straight pattern, gunmetal
External thread, PN 8bar, Tmax 200°C
2) Thermostatic head with immersion sensor
Setpoint range 25°C to 70°C
Capillary tube length 2m, capillary tube seal compression fitting R¾
Sensor dimension 16x210mm
3) Immersion sleeve HSF R¾×220mm
4) 2x screw nipple insert, flat sealing, R1¼
Performance data
DN32, DpN 100mbar, V'maxN 3,95m³/h, Kvs 12,5, straight pattern, gunmetal