DUVbox DN25s 2x3 VR 3

Item no. 001 409 Manifold products
For highly efficient two-zone charging of a buffer storage tank by a heat generator with minimum circulation in heating mode and with priority domestic hot water preparation (three-chamber manifold)

Recommended accessories

								

Schl KuH DN32-50 set

996167
								

ISO KuH DN32 G1½(i)xRp1¼

996086

Further information?

Further questions?

Contact technical support
					

Configure product variant

Nominal width

DN25s

Performance class

Producer circuit (LT):
Kvs = 10.4 • V'max[250mbar] = 5.2m³/h
Q'max[20K] = 121kW • Q'max[10K] = 60kW

Flow direction producer

Flow direction Producer Left

Pump flange

on the heating circuit flow (3)

Product documentation

Assembly instructions

Assembly instructions: For specialist partners only.
Please log in here or register here

Actuator three-way mixer: For specialist partners only.
Please log in here or register here

Spare parts drawing

Spare parts drawing For specialist partners only.
Please log in here or register here

Data sheet

001409_DBL_2021-12-21.pdf

GAEB

001409.D81

Tender text

Baunach article master data Version: 10.05.24

BAFA funding opportunity as part of heating system optimisation through hydraulic balancing and installation of separate control technology

rendeMIX double changeover valve consisting of two 3-way changeover valves DN32×G1½(a) Ms58, plug and cover Ms58

For highly efficient two-zone charging of a buffer storage tank by a heat generator with minimum circulation in heating mode and with priority domestic hot water preparation (three-chamber manifold)

2 actuators EMS 90-2P, 230V~ 50Hz 2.3VA 2-point signal, 6Nm (240h), 90°, 60s, right-hand closing, grey adapter

Switching assembly with 3 connections to the buffer tank, CuØ35×1, pipe spacing to the heat generator 200mm, pipe spacing to the buffer tank 100mm, DN32×G1½(a) flat

1 integrated gravity brake/backflow preventer, Dp10mbar

Generator circuit (LT): Kvs = 10.4 - V'max[250mbar] = 5.2m³/h - Q'max[20K] = 121kW - Q'max[10K] = 60kW - Leakage rate < 0,1%

5 Thermometers 0-120°C, Ø63mm, soldering sleeves Ms58

5 Ball valve screw connections, DN32 passage, PN25, G1½(i)×Rp1¼ flat-sealing, stuffing box, spindle with square drive SW25

Insulating moulded tray EPP 40g/l, black, 300×450mm, quick assembly kit

With pump flange G1½(i) for pump DN25 at heat generator return (3)

Assembly does NOT include pump compensator - PAS L180 (Part No.: 001 338)

Assembly does not contain a pump

Model DN 25 - manifold assembly for manifold connection from RIGHT, PN 10bar, Tmax 120°C

Performance data

Generator circuit (LT): Kvs = 10.4 - V'max[250mbar] = 5.2m³/h - Q'max[20K] = 121kW - Q'max[10K] = 60kW - Leakage rate < 0,1%

Baunach