Product search
rJET DN25s 3x4 R 1
Accessories needed
![]() |
ST DN25s AD100 P60 LR 5001138 |
![]() |
ST DN25s AD100 P60 LR001136 |
Recommended accessories
|
ISO KuHV DN25s G1½(i)xRp1996085 |
Configure product variant
Nominal width
Performance class
Kvs = 9.2 V'max[100mbar] = 2.9m³/h
Q'max[20K] = 67kW
Mixing circuit (LT) with ST DN25s:
Kvs = 7.2 V'max[100mbar] = 2.3m³/h
Q'max[10K] = 27kW
Flow direction producer
Pump flange
Product documentation
Assembly instructions
Assembly instructions: For specialist partners only.
Please log in here or register here
Actuator multi-way mixer: For specialist partners only.
Please log in here or register here
Spare parts drawing
Spare parts drawing For specialist partners only.
Please log in here or register here
Data sheet
GAEB
Tender text
Baunach article master data Version: 19.11.24
BAFA funding opportunity as part of heating system optimisation through hydraulic balancing and installation of separate control technology
rendeMIX multi-port mixing manifold with 3/2-way tangential mixing valve DN25×G1½(a) MsGuss (adapter red), plug and cover Ms58
For highly efficient two-zone unloading of a buffer tank in a mixed low-temperature circuit by means of highly efficient operation of a system separation via flow control from the differential pressure of the pump in the heat generator circuit (i.e. without an additional pump in the primary circuit of the system separation!) with highly efficient use of the return flow of an unmixed high-temperature circuit.
Actuator EMS 240, 230V~ 50Hz 3.5VA 3-point signal, 5Nm (240h), 240°, 93s
Two-circuit manifold assembly with 3 connections to the heat generator (buffer or boiler with flue gas heat exchanger), CuØ35×1, pipe spacing 100mm, DN32×G1½(a) flat
1 integrated backflow preventer, Dp10mbar and 1 integrated return differential pressure regulator, Dp50-70mbar
Direct heating circuit (HT): Kvs = 9.2 - V'max[100mbar] = 2.9m³/h - Q'max[20K] = 67kW - Mixed heating circuit (NT) with ST DN25s: Kvs = 7.2 - V'max[100mbar] = 2.3m³/h - Q'max[10K] = 27kW - Leakage rate < 0,1%
7 Thermometer 0-120°C, Ø63mm, soldering sleeves Ms58
7 Ball valve screw connections, DN25s passage, PN20, G1½(i)×Rp1 flat-sealing, stuffing box, spindle with aluminium T-handle
Insulating moulded tray EPP 40g/l, black, 450×450mm, quick assembly kit
With pump flange G1½(i) for pump DN25 on heat generator flow (1)
Assembly includes ONE pump balancing piece - PAS L180 - with G1½(a)×G1½(i) fittings for balancing one pump DN25, length 180mm, insulated (part no.: 001 338).
Assembly does not contain a pump
Model DN 25 - strong version, PN 10bar, Tmax 120°C
ATTENTION: CANNOT BE USED WITHOUT SYSTEM SEPARATION!
Performance data
Direct heating circuit (HT): Kvs = 9.2 - V'max[100mbar] = 2.9m³/h - Q'max[20K] = 67kW - Mixed heating circuit (NT) with ST DN25s: Kvs = 7.2 - V'max[100mbar] = 2.3m³/h - Q'max[10K] = 27kW - Leakage rate < 0,1%