Product search
RTB DN25 T0-50 Adjustment set (slow)
Recommended accessories
Thermostatic head setting limit999920 |
Configure product variant
Performance class
V'max[100mbar] = 1.8m³/h
Q'max = 42kW [20K] = 17l/min [10/45°C]
Product documentation
Tender text
Baunach article master data Version: 22.11.23
BAFA funding opportunity within the scope of heating system optimisation through hydraulic balancing and installation of technology for volume flow control
Thermostatic return temperature limiter with adjustable maximum temperature, with approx. 1% fixed minimum flow rate
For automatic, hydraulic balancing of individual heat exchangers such as single-pipe heating circuits, radiant ceiling panels and swimming pool heat exchangers. Due to inertia, not suitable for air heaters and ventilation and air-conditioning systems.
consisting of:
1) Valve lower section actively closing VUS D 250 with approx. 1% fixed minimum flow rate
DN25, DpN 100mbar, V'maxN 1.9 m³/h, Kvs 5.7 Straight pattern, nickel-plated red brass
Inlet sleeve Rp1, outlet fitting conical G1¼(i) × R1
PN 10bar, Tmax 120°C, (part no. 996 011)
2) Thermostatic head with contact sensor TK-KF
Setpoint range 0°C to 50°C
PN 10bar, Tmax 90°C (part no. 996 028)
3) Syringe with thermal paste (part no. 000 598)
Performance data
DN25, DpN 100mbar, V'maxN 1.9 m³/h, Kvs 5.7 Straight pattern, nickel-plated red brass