RTB DN25 T0-50 Adjustment set (slow)

Item no. 996 207 Valve technology
For automatic, hydraulic balancing of individual heat exchangers such as single-pipe heating circuits, radiant ceiling panels and swimming pool heat exchangers. Due to inertia, not suitable for air heaters and ventilation and air-conditioning systems.

Recommended accessories

								

Thermostatic head setting limit

999920

Further information?

Further questions?

Contact technical support
					

Configure product variant

Nominal width

DN25

Product documentation

Tender text

Baunach article master data Version: 22.11.23

BAFA funding opportunity within the scope of heating system optimisation through hydraulic balancing and installation of technology for volume flow control

Thermostatic return temperature limiter with adjustable maximum temperature, with approx. 1% fixed minimum flow rate

For automatic, hydraulic balancing of individual heat exchangers such as single-pipe heating circuits, radiant ceiling panels and swimming pool heat exchangers. Due to inertia, not suitable for air heaters and ventilation and air-conditioning systems.

consisting of:

1) Valve lower section actively closing VUS D 250 with approx. 1% fixed minimum flow rate

DN25, DpN 100mbar, V'maxN 1.9 m³/h, Kvs 5.7 Straight pattern, nickel-plated red brass

Inlet sleeve Rp1, outlet fitting conical G1¼(i) × R1

PN 10bar, Tmax 120°C, (part no. 996 011)

2) Thermostatic head with contact sensor TK-KF

Setpoint range 0°C to 50°C

PN 10bar, Tmax 90°C (part no. 996 028)

3) Syringe with thermal paste (part no. 000 598)

Performance data

DN25, DpN 100mbar, V'maxN 1.9 m³/h, Kvs 5.7 Straight pattern, nickel-plated red brass

Baunach