rMIX DN32 2x3 VL 5

Item no. 001 676 Manifold products
For highly efficient two-zone charging of a buffer storage tank by a heat generator with return temperature increase as a mixing circuit (three-chamber manifold).

Recommended accessories

								

REG-FWR

996020
								

Schl KuH DN32-50 set

996167
								

ISO KuH DN32 G1½(i)xRp1¼

996086

Further information?

Further questions?

Contact technical support
					

Configure product variant

Nominal width

DN32

Performance class

Producer circuit (HT-RLA):
Kvs = 18.9 • V'max[250mbar] = 9.5m³/h
Q'max[20K] = 221kW • Q'max[10K] = 110kW

Flow direction producer

Flow direction Producer Left

Flow direction consumer

Flow direction Consumer Right

Pump flange

at the mixing circuit (5)

Product documentation

Assembly instructions

Assembly instructions: For specialist partners only.
Please log in here or register here

Actuator multi-way mixer: For specialist partners only.
Please log in here or register here

Spare parts drawing

Spare parts drawing For specialist partners only.
Please log in here or register here

Data sheet

001676_DBL_2021-12-21.pdf

GAEB

001676.D81

Tender text

Baunach article master data Version: 10.05.24

BAFA funding opportunity as part of heating system optimisation through hydraulic balancing and installation of separate control technology

rendeMIX multi-port mixing manifold with 3/3-way tangential mixing valve DN32×G1½(a) MsGuss (red adapter), plug and cover Ms58

For highly efficient two-zone charging of a buffer storage tank by a heat generator with return temperature increase as a mixing circuit (three-chamber manifold).

Actuator EMS 240, 230V~ 50Hz 3.5VA 3-point signal, 5Nm (240h), 240°, 93s

Return lifting group with 3 connections to the buffer tank, CuØ35×1, pipe spacing to the buffer tank 100mm, pipe spacing to the mixing circuit 200mm, DN32×G1½(a) flat

2 integrated gravity brakes/backflow preventer, Dp10mbar

Generator circuit (HT-RLA): Kvs = 18.9 - V'max[250mbar] = 9.5m³/h - Q'max[20K] = 221kW - Q'max[10K] = 110kW - Leakage rate < 0,1%

5 Thermometers 0-120°C, Ø63mm, soldering sleeves Ms58

5 Ball valve screw connections, DN32 passage, PN25, G1½(i)×Rp1¼ flat-sealing, stuffing box, spindle with square drive SW25

Insulating moulded tray EPP 40g/l, black, 300×450mm, quick assembly kit

With pump flange G1½(i) for pump DN25 on mixed heat generator return (5)

Assembly does NOT include pump compensator - PAS L180 (Part No.: 001 338)

Assembly does not contain a pump

Model DN 32 - manifold assembly for manifold connection from LEFT, PN 10bar, Tmax 120°C

Performance data

Generator circuit (HT-RLA): Kvs = 18.9 - V'max[250mbar] = 9.5m³/h - Q'max[20K] = 221kW - Q'max[10K] = 110kW - Leakage rate < 0,1%

Baunach