rSYS DN25s 3x4 R

Item no. 001 623 Two-zone discharge
For highly efficient two-zone unloading of a buffer tank in a mixed low-temperature circuit with highly efficient use of the return flow of an unmixed high-temperature circuit by means of highly efficient operation of a system separation via flow control

Accessories needed

								

ST DN25s AD100 P60 LR 5

001138
								

ST DN25s AD100 P60 LR

001136

Recommended accessories

								

ISO KuHV DN25s G1½(i)xRp1

996085

Further information?

Further questions?

Contact technical support
					

Configure product variant

Nominal width

DN25s

Performance class

Direct heating circuit (HT):
Kvs = 11.9 • V'max[100mbar] = 3.8m³/h
Q'max[20K] = 88kW
Mixing circuit (LT) for ST on-site:
Kvs = 9.7 • V'max[100mbar] = 3.1m³/h
Q'max[10K] = 36kW

Flow direction producer

Flow direction Producer Right

Product documentation

Assembly instructions

Assembly instructions: For specialist partners only.
Please log in here or register here

Actuator multi-way mixer: For specialist partners only.
Please log in here or register here

Spare parts drawing

Spare parts drawing For specialist partners only.
Please log in here or register here

Tender text

Baunach article master data Version: 22.11.23

BAFA funding opportunity as part of heating system optimisation through hydraulic balancing and installation of separate control technology

rendeMIX multi-port mixing manifold with 3/2-way tangential mixing valve DN25×G1½(a) MsGuss (adapter red), plug and cover Ms58

For highly efficient two-zone unloading of a buffer tank in a mixed low-temperature circuit with highly efficient use of the return flow of an unmixed high-temperature circuit by means of highly efficient operation of a system separation via flow control

Actuator EMS 240, 230V~ 50Hz 3.5VA 3-point signal, 5Nm (240h), 240°, 93s

Two-circuit manifold assembly with 3 connections to the heat generator (buffer or boiler with flue gas heat exchanger), CuØ35×1, pipe spacing 100mm, DN32×G1½(a) flat

3 integrated gravity brakes/backflow preventer, Dp10mbar

Direct heating circuit (HT): Kvs = 11.9 - V'max[100mbar] = 3.8m³/h - Q'max[20K] = 88kW - Mixed circuit (NT) for system separation on site: Kvs = 9.7 - V'max[100mbar] = 3.1m³/h - Q'max[10K] = 36kW - Leakage rate < 0,1%

7 Thermometer 0-120°C, Ø63mm, soldering sleeves Ms58

7 Ball valve screw connections, DN25s passage, PN20, G1½(i)×Rp1 flat-sealing, stuffing box, spindle with aluminium T-handle

Insulating moulded tray EPP 40g/l, black, 450×450mm, quick assembly kit

Without pump flanges

Assembly does NOT include pump compensator - PAS L180 (Part No.: 001 338)

Assembly does not contain a pump

Model DN 25 - strong version, PN 10bar, Tmax 120°C

ATTENTION: CANNOT BE USED WITHOUT SYSTEM SEPARATION!

Performance data

Direct heating circuit (HT): Kvs = 11.9 - V'max[100mbar] = 3.8m³/h - Q'max[20K] = 88kW - Mixed circuit (NT) for system separation on site: Kvs = 9.7 - V'max[100mbar] = 3.1m³/h - Q'max[10K] = 36kW - Leakage rate < 0,1%

Baunach