rSYS DN25 2x4 RT 1-a

Item no. 001 511 Return flow utilisation
TWIN assembly for the expansion of a rendeMIX 2x4 assembly by an additional low-temperature mixing circuit with return use of the high-temperature circuit and highly efficient operation of a system separation via flow control

Accessories needed

								

ST DN25 AD100 P40 LL 5

001008
								

ST DN25 AD100 P40 LL

001006

Further information?

Further questions?

Contact technical support
					

Configure product variant

Nominal width

DN25

Performance class

Downstream assembly (HT):
Kvs = 6.5 • V'max[100mbar] = 2.1m³/h
Q'max[20K] = 49kW
Additional mixing circuit (NT) with ST DN25:
Kvs = 5.7 • V'max[100mbar] = 1.8m³/h
Q'max[10K] = 21kW

Flow direction producer

Flow direction Producer Right

Pump flange

Product documentation

Assembly instructions

Assembly instructions: For specialist partners only.
Please log in here or register here

Actuator multi-way mixer: For specialist partners only.
Please log in here or register here

Tender text

Baunach article master data Version: 22.11.23

BAFA funding opportunity within the scope of heating system optimisation by replacing heating circulating pumps with high-efficiency circulating pumps.

rendeMIX multi-port mixing manifold with 3/2-way tangential mixing valve DN25×G1½(a) MsGuss (adapter green), plug and cover Ms58

TWIN assembly for the expansion of a rendeMIX 2x4 assembly by an additional low-temperature mixing circuit with return use of the high-temperature circuit and highly efficient operation of a system separation via flow control

Actuator EMS 240, 230V~ 50Hz 3.5VA 3-point signal, 5Nm (240h), 240°, 93s

Dual circuit manifold assembly with 2 connections to the heat source and 4 connections to the heat sinks, CuØ35×1, DN32×G1½(a) flat, pipe spacing 100mm.

1 integrated gravity brake/backflow preventer, Dp10mbar

Downstream assembly (HT): Kvs = 6.5 - V'max[100mbar] = 2.1m³/h - Q'max[20K] = 49kW - Additional mixing circuit (LT) with ST DN25: Kvs = 5.7 - V'max[100mbar] = 1.8m³/h - Q'max[10K] = 21kW - Leakage rate < 0,1%

4 thermometers 0-120°C, Ø63mm, soldering sleeves Ms58

2 ball valve screw connections, DN25 passage, PN32, G1½(i)×Rp1 flat-sealing, stuffing box, sealing hole, spindle with aluminium wing handle

Insulating moulded tray EPP 40g/l, black, 450×450mm, quick assembly kit

With pump flange G1½(i) for pump DN25 on heat generator flow (1)

Assembly does NOT include pump compensator - PAS L180 (Part No.: 001 338)

With built-in high-efficiency Grundfos UPM3 pump, DN25, 130mm, H 5-6mWS, 230V~ 50Hz, 2m connection cable, EEI < 0,2

Model DN 25 - light version, PN 10bar, Tmax 120°C

ATTENTION: CANNOT BE USED WITHOUT SYSTEM SEPARATION!

Performance data

Downstream assembly (HT): Kvs = 6.5 - V'max[100mbar] = 2.1m³/h - Q'max[20K] = 49kW - Additional mixing circuit (LT) with ST DN25: Kvs = 5.7 - V'max[100mbar] = 1.8m³/h - Q'max[10K] = 21kW - Leakage rate < 0,1%