rMIX DN25s 3x3C VL 6

Item no. 001 440 Manifold products
For highly efficient two-zone charging of a buffer tank by a heat generator with return temperature increase and separate flue gas condenser or two return connections (three-chamber manifold).

Accessories needed

								

VTB DN32s T25-70 Condenser Set

996106
								

VTB DN40s T25-70 Condenser Set

996107
								

VTB DN50s T25-70 Condenser Set

996108

Recommended accessories

								

REG-FWR

996020
								

Schl KuH DN32-50 set

996167
								

ISO KuH DN32 G1½(i)xRp1¼

996086

Further information?

Further questions?

Contact technical support
					

Configure product variant

Nominal width

DN25s

Performance class

Producer circuit (HT-RLA):
Kvs = 11.6 • V'max[250mbar] = 5.8m³/h
Q'max[10K] = 135kW
Condenser circuit (LT):
Kvs = 9.2 • V'max[250mbar] = 4.6m³/h
Q'max[20K] = 107kW

Flow direction producer

Flow direction Producer Left

Pump flange

on the heat generator flow (6)

Product documentation

Assembly instructions

Assembly instructions: For specialist partners only.
Please log in here or register here

Actuator multi-way mixer: For specialist partners only.
Please log in here or register here

Spare parts drawing

Spare parts drawing For specialist partners only.
Please log in here or register here

Data sheet

001440_DBL_2021-12-21.pdf

Tender text

Baunach article master data Version: 10.05.24

BAFA funding opportunity as part of heating system optimisation through hydraulic balancing and installation of separate control technology

rendeMIX multi-port mixing manifold with 3/3-way tangential mixing valve DN25×G1½(a) MsGuss (red adapter), plug and cover Ms58

For highly efficient two-zone charging of a buffer tank by a heat generator with return temperature increase and separate flue gas condenser or two return connections (three-chamber manifold).

Actuator EMS 240, 230V~ 50Hz 3.5VA 3-point signal, 5Nm (240h), 240°, 93s

Mixer assembly with 3 connections to the heat source and separate charging circuit output, CuØ35×1, pipe spacing 100mm, DN32×G1½(a) flat

1 integrated backflow preventer, Dp10mbar and 1 external flow differential pressure regulator, Dp80mbar mounted on the mixing circuit flow (5) in Ms58 adapter L 90mm

Erzeugerkreis (HT-RLA): Kvs = 11,6 • V'max[250mbar] = 5,8m³/h • Q'max[10K] = 135kW • Leckrate < 0,1% - Condenserkreis (NT): Kvs = 9,2 • V'max[250mbar] = 4,6m³/h • Q'max[20K] = 107kW

6 Thermometers 0-120°C, Ø63mm, soldering sleeves Ms58

6 ball valve screw connections, DN32 passage, PN25, G1½(i)×Rp1¼ flat-sealing, stuffing box, spindle with square drive SW25

Insulating moulded tray EPP 40g/l, black, 300×450mm, quick assembly kit

With pump flange G1½(i) for pump DN25 on heat generator flow (6)

Assembly includes ONE pump balancing piece PAS L180 (part no.: 001 338) and ONE pump balancing piece PAS L90 (part no.: 001 347) - both with screwed connections G1½(a)×G1½(i) for balancing a pump DN25, length 180mm/90mm, insulated.

Assembly does not contain a pump

Model DN 25 - manifold assembly for manifold connection from LEFT, PN 10bar, Tmax 120°C

ATTENTION: CANNOT BE USED WITHOUT FLOW TEMPERATURE LIMITER (VTB) THERMOSTATIC VALVE! Available in DN32s (part no. 996 106), DN40s (part no. 996 107) or DN50s (part no. 996 108).

Performance data

Erzeugerkreis (HT-RLA): Kvs = 11,6 • V'max[250mbar] = 5,8m³/h • Q'max[10K] = 135kW • Leckrate < 0,1% - Condenserkreis (NT): Kvs = 9,2 • V'max[250mbar] = 4,6m³/h • Q'max[20K] = 107kW

Baunach