Valve technology
Enables a constant flow temperature for condensing boilers (WITHOUT minimum flow rate / WITHOUT delta T limitation!) with variable boiler output or fluctuating return flow temperature due to variable water volume at full condensing boiler utilization
BAFA funding opportunity for heating system optimization through hydraulic balancing and the installation of flow control technology
Thermostatic flow temperature limiter with adjustable minimum temperature, featuring a fixed minimum flow rate of approx. 1%
Enables, in condensing boilers (WITHOUT minimum flow rate / WITHOUT Delta-T limitation!) to maintain a constant flow temperature at variable boiler output or fluctuating return temperature by adjusting the water flow rate while fully utilizing condensing efficiency
Consisting of:
1) Actively opening valve base VUO D 200 with fixed minimum flow rate DN20
Kvs = 3.2
V'max [250 mbar] = 1.6 m³/h<br/>Q'max = 37 kW [20 K] = 93 kW [50 K]<br/>Straight-through design, nickel-plated red brass, EPDM seal, inlet nipple R¾×Rp¾ outlet socket<br/>inlet-side conical screw connection G1, PN 10 bar, Tmax 120°C, (Part No. 996 004)<br/>2) Thermostat head with TK-TF immersion sensor, setpoint range 60°C to 90°C<br/>capillary tube length 2 m, immersion sensor length 175 mm, Ø 11 mm, response time approx. 60 s<br/>PN 10 bar, Tmax 100°C (Part No. 996 014)<br/>3) Immersion sleeve HSF R½×186 mm, (Part No. 996 015)<br/>4) Connection fittings:<br/>a) Black reducer R1×Rp¾ (Part No. 996 076)<br/>b) Black reducer nipple R1×R¾ (Part No. 996 071)<br/>5) Black T-fitting, TsF 1x1x½ (Part No. 996 056)<br/>6) Black double nipple, NDs 1x1 (replacement part no. 996 065)
Kvs = 3.2
V'max [250 mbar] = 1.6 m³/h
Q'max = 37 kW [20 K] = 93 kW [50 K]