rSTOR C
For direct connection of up to four rendeMIX modules via two sets of four ball valve T-connectors
BAFA funding opportunity for heating system optimization through hydraulic balancing and the installation of separate control technology
Vertical steel buffer tank with a nominal volume of 1,000 liters
for direct connection of up to four rendeMIX modules via two sets of four ball valve T-connections
max. Operating temperature Tmax 95°C, max. operating pressure PN 3 bar
4 baffle plates to reduce flow-induced turbulence, velocity reduction 1:20
3 zones for temperature-differentiated stratification maintenance for domestic hot water, high-temperature heating, and low-temperature heating/solar, volume distribution 1/3 each; three consecutively numbered dual-clamp temperature sensor mounting points with steel springs per zone<br/>Tank: V = 1,000 L, height without/with insulation 2,012 mm/2,153 mm, tilting dimension (without insulation) 2,074 mm, Ø without/with insulation 790/1,040 mm<br/>Multi-layer, non-diffusion-tight insulation consisting of 125 mm expanded polystyrene (EPS) and polyester fiber fleece, top layer of 1 mm impact-resistant polystyrene with hook-lock strip, energy efficiency class B<br/>All connections fully insulated with molded parts made of expanded polypropylene (EPP)<br/>Connections:
2 x 4 x Rp1¼ for two ball valve T-connector 4-piece sets DN32 R1¼xG1½(i), 2 x Rp1 for solar flow (150-liter water storage tank)/circulation lance, 2 x Rp¾ for solar return/drain, 1 x Rp½ for venting<br/>Accessories included:
3 x capillary tube thermometers 0–120°C – Class 2.5 – Ø 57 mm, 1 x R½ vent valve with hose barb and approx. 2 m of silicone hose, 3 x adjustable feet Ø 64 mm for vertical alignment, 1 x KFE drain valve R¾, 1 x black pipe plug R¾, 2 x black pipe plugs R1, 1 x Baunach rSTOR sticker for application on the insulation
Container: V = 1,000 L, height without/with insulation 2,012 mm/2,153 mm, tipping dimension (without insulation) 2,074 mm, diameter without/with insulation 790/1,040 mm