For highly efficient two-zone loading of a buffer cylinder by a heat generator with return temperature increase as a mixing circuit (three-chamber manifold)
BAFA funding opportunity for heating system optimization through hydraulic balancing and the installation of separate control technology<br/>rendeMIX multi-port mixing manifold consisting of two cascaded 3-way mixing valves DN50×FlPN6 gray cast iron, valves and covers made of gray cast iron<br/>For highly efficient two-zone charging of a buffer tank by a heat generator with return temperature increase as a mixing circuit (three-chamber manifold)
EMS 90-3P actuator, 230V~ 50Hz 3.5VA 3-point signal, 20Nm, 90°, 95s<br/>Return temperature boost unit with 3 connections to the buffer tank, DN50, pipe spacing to the buffer tank 290 mm, pipe spacing to the mixing circuit 580 mm, DN50×FlPN6<br/>without integrated gravity brake/backflow preventer<br/>Generator circuit (HT-RLA): Kvs = 28.3 • V'max[250 mbar] = 14 m³/h • Q'max[20 K] = 329 kW • Q'max[10K] = 164 kW • Leak rate < 0.1%
Without thermometer
Without ball valve fitting
Without insulation shell and quick-installation kit
With DN50 PN6 pump flange<br/>Assembly does NOT include pump compensator – PAS L180 (Part No.: 001 338)<br/>Assembly does not include a pump<br/>Model DN 50 – Manifold assembly for manifold connection from the LEFT, PN 6 bar, Tmax 120°C
Generator circuit (HT-RLA): Kvs = 28.3 • V'max[250mbar] = 14m³/h • Q'max[20K] = 329kW • Q'max[10K] = 164kW • Leakage rate < 0.1%