Two-zone discharge
For highly efficient two-zone discharging of a buffer cylinder through a mixing circuit
Specialist partner access required
Specialist partner access required
Specialist partner access required
BAFA Funding Opportunity for Heating System Optimization Through Hydraulic Balancing and Installation of Separate Control TechnologyrendeMIX Multi-Port Mixing Manifold with 3/3-Way Tangential Mixing Valve DN32×G1½(a) MsGuss (red adapter), valve and cover Ms58For highly efficient two-zone discharge of a buffer tank via a mixing circuitEMS 240 actuator, 230 V AC, 50 Hz, 3.5 VA, 3-point signal, 5 Nm (240 h), 240°, 93sSingle-circuit mixer assembly with 3 connections to the heat source, Cu Ø35×1, DN32×G1½(a) flat, pipe spacing to the heat source 100 mm, pipe spacing to the mixing circuit 200 mm2 integrated gravity brakes/backflow preventers, Dp 10 mbarMixing circuit (NT): Kvs = 18.9 • V'max[100 mbar] = 6 m³/h • Q'max[20 K] = 140 kW • Q'max[10 K] = 70 kW • Leak rate < 0.1%5 thermometers 0–120°C, Ø63mm, solder sleeves Ms585 ball valve fittings, straight-through DN32, PN25, G1½(i)×Rp1¼ flat-seal, stuffing box, stem with square drive SW25EPP insulation mold, 40 g/l, black, 300×450 mm, Quick-installation kitWith pump flange G1½(i) for DN25 pump on the mixing circuit supply line (5)Assembly does NOT include a pump compensator – PAS L180 (Part No.: 001 338)Assembly does not include a pumpModel DN 32, PN 10 bar, Tmax 120°C
Mixing circuit (NT): Kvs = 18.9 • V'max[100mbar] = 6m³/h • Q'max[20K] = 140kW • Q'max[10K] = 70kW • Leakage rate < 0.1%