Return utilization
For highly efficient use of the return flow of an unmixed high temperature circuit in a mixed low temperature circuit by means of highly efficient operation of a system separation via flow control on a condensing boiler, a stratified storage tank or a heat transfer station
Specialist partner access required
Specialist partner access required
Specialist partner access required
BAFA Funding Opportunity for Heating System Optimization Through Hydraulic Balancing and Installation of Separate Control Technology
rendeMIX Multi-Port Mixing Manifold with 3/2-Way Tangential Mixing Valve DN25×G1½(a) Ms Cast Iron (red adapter), valve and cover Ms58
For highly efficient utilization of the return flow from an unmixed high-temperature circuit in a mixed low-temperature circuit through highly efficient operation of a system separation via flow control on a condensing boiler, a stratified storage tank, or a heat transfer station
Actuator EMS 240, 230 V AC, 50 Hz, 3.5 VA, 3-point signal, 5 Nm (240 h), 240°, 93s
Dual-circuit manifold assembly with 2 connections to the heat source and 4 connections to the heat sinks, Cu Ø35×1, DN32×G1½(a) flat, pipe spacing 100 mm
3 integrated gravity brakes/backflow preventers, Dp 10 mbar
Direct heating circuit (HT): Kvs = 11.9 × V'max[100 mbar] = 3.8 m³/h × Q'max[20 K] = 88 kW - Mixing circuit (NT) with ST DN25s: Kvs = 7.2 × V'max[100 mbar] = 2.3 m³/h × Q'max[10 K] = 27 kW × Leak rate < 0.1%<br/>6 thermometers 0–120°C, Ø63mm, solder sleeves Ms58<br/>6 ball valve fittings, straight-through DN25s, PN20, G1½(i)×Rp1 flat-seal, stuffing box, stem with nylon T-handle<br/>EPP insulation mold, 40 g/l, black, 450×450 mm, Quick-installation kit<br/>With G1½(i) pump flanges for DN25 pumps on the unmixed heating (3) and mixing circuit supply (5)
Assembly includes TWO pump compensators—PAS L180—with G1½(a)×G1½(i) threaded connections to compensate for a DN25 pump, length 180 mm, insulated (Part No.: 001 338)<br/>With built-in, highly efficient Grundfos UPM3 pump, DN25, 130 mm, H 5–6 mWS, 230 V~ 50 Hz, 2 m connection cable, EEI < 0.2<br/>Model DN 25 – heavy-duty version, PN 10 bar, Tmax 120°C<br/>CAUTION: CANNOT BE USED WITHOUT SYSTEM ISOLATION!
Direct heating circuit (HT): Kvs = 11.9 • V'max[100mbar] = 3.8m³/h • Q'max[20K] = 88kW - Mixing circuit (NT) with ST DN25s: Kvs = 7.2 • V'max[100mbar] = 2.3m³/h • Q'max[10K] = 27kW • Leakage rate < 0.1%