rSTOR C
For highly efficient two-zone discharge of an rSTOR C buffer tank via a mixing circuit; connection ABOVE a ball valve connection set
Specialist partner access required
Specialist partner access required
BAFA Funding Opportunity for Heating System Optimization Through Hydraulic Balancing and Installation of Separate Control Technology<br/>rendeMIX Multi-Port Mixing Manifold with 3/3-Way Tangential Mixing Valve DN25×G1½(a) MsGuss (red adapter), valve and cover Ms58<br/>For highly efficient two-zone discharge of an rSTOR C buffer tank via a mixing circuit; connection ABOVE a ball valve connection set<br/>Actuator EMS 240, 230V~ 50Hz 3.5VA 3-point signal, 5Nm (240h), 240°, 93s<br/>Single-circuit mixer assembly with 3 connections to the heat source, Cu Ø35×1, DN32×G1½(a) flat, pipe spacing to the heat source 100 mm, pipe spacing to the mixing circuit 200 mm<br/>2 integrated gravity brakes/backflow preventers, Dp 10 mbar<br/>Mixing circuit (NT): Kvs = 12.9 • V'max[100 mbar] = 4.1 m³/h • Q'max[20 K] = 95 kW • Q'max[10 K] = 48 kW • Leak rate < 0.1%<br/>5 thermometers 0–120°C, Ø63mm, solder sleeves Ms58<br/>2 ball valve fittings, straight-through DN25s, PN20, G1½(i)×Rp1 flat-seal, stuffing box, stem with nylon T-handle<br/>EPP insulation mold, 40 g/l, black, 300×450 mm, quick-assembly kit<br/>With G1½(i) pump flange for DN25 pump on the mixing circuit supply line (5)<br/>Assembly does NOT include pump compensator – PAS L180 (Part No.: 001 338)<br/>With blind fitting consisting of a G1½ brass union nut, stainless steel washer, and insulating cap<br/>Model DN 25 – lightweight version, PN 10 bar, Tmax 120°C
Mixing circuit (NT): Kvs = 12.9 • V'max[100mbar] = 4.1m³/h • Q'max[20K] = 95kW • Q'max[10K] = 48kW • Leakage rate < 0.1%