rSTOR C
For highly efficient two-zone discharge of an rSTOR C buffer tank in a mixed low-temperature circuit, making highly efficient use of the return flow from an unmixed high-temperature circuit; connection ABOVE a ball valve connection set
Specialist partner access required
Specialist partner access required
BAFA Funding Opportunity for Heating System Optimization Through Hydraulic Balancing and Installation of Separate Control TechnologyrendeMIX Multi-Port Mixing Manifold with 3/3-Way Tangential Mixing Valve DN25×G1½(a) MsGuss (red adapter), valve body and cover Ms58For highly efficient two-zone discharge of an rSTOR C buffer tank in a mixed low-temperature circuit with highly efficient utilization of the return flow from an unmixed high-temperature circuit, Connection ABOVE a ball valve connection setActuator EMS 240, 230V~ 50Hz 3.5VA 3-point signal, 5Nm (240h), 240°, 93sTwo-circuit manifold assembly with 3 connections to the heat generator (buffer tank or boiler with flue gas heat exchanger), Cu Ø35×1, pipe spacing 100 mm, DN32×G1½(a) flat3 integrated gravity brakes/backflow preventers, Dp 10 mbarDirect heating circuit (HT): Kvs = 11.9 • V'max[100 mbar] = 3.8 m³/h • Q'max[20 K] = 88 kW - Mixing circuit (NT): Kvs = 12.9 • V'max[100 mbar] = 4.1 m³/h • Q'max[10 K] = 48 kW • Leak rate < 0.1%7 thermometers 0–120°C, Ø63 mm, solder sleeves Ms584 ball valve fittings, straight-through DN25s, PN20, G1½(i)×Rp1 flat-seal, stuffing box, stem with nylon T-handleInsulating molded shell, EPP 40 g/l, black, 450×450 mm, Quick-assembly kitWithout pump flangesAssembly does NOT include pump compensator – PAS L180 (Part No.: 001 338)With blind fitting consisting of a G1½ brass union nut and a stainless steel washerModel DN 25 – heavy-duty version, PN 10 bar, Tmax 120°C
Direct heating circuit (HT): Kvs = 11.9 • V'max[100mbar] = 3.8m³/h • Q'max[20K] = 88kW - Mixing circuit (NT): Kvs = 12.9 • V'max[100mbar] = 4.1m³/h • Q'max[10K] = 48kW • Leakage rate < 0.1%