For highly efficient two-zone loading of a buffer cylinder by a heat generator with minimum circulation in heating mode and with priority DHW heating (three-chamber manifold)
Specialist partner access required
Specialist partner access required
BAFA funding opportunity for heating system optimization through hydraulic balancing and the installation of separate control technology<br/>rendeMIX double-switch valve consisting of two DN32×G1½(a) Ms58 3-way switching valves, valve body and cover Ms58<br/>For highly efficient two-zone charging of a buffer tank by a heat generator with minimum circulation in heating mode and during priority domestic hot water production (three-chamber manifold)
2 EMS 90-2P actuators, 230V~ 50Hz 2.3VA 2-point signal, 6Nm (240h), 90°, 60s, left-closing, gray adapter
Switching assembly with 4 connections to the buffer tank, Cu Ø35×1, pipe spacing to the heat generator 200 mm, pipe spacing to buffer tank 100 mm, DN32×G1½(a) flat<br/>1 integrated gravity brake/backflow preventer, Dp 10 mbar<br/>Generator circuit (NT): Kvs = 10.4 • V'max[250 mbar] = 5.2 m³/h • Q'max[20 K] = 121 kW • Q'max[10 K] = 60 kW • Leak rate < 0.1%<br/>6 thermometers 0–120°C, Ø63mm, solder sleeves Ms58<br/>6 ball valve fittings, straight-through DN32, PN25, G1½(i)×Rp1¼ flat-seal, stuffing box, stem with square drive SW25<br/>EPP insulation mold 40 g/l, black, 450×450 mm, Quick-installation kit<br/>With pump flange G1½(i) for DN25 pump on the unmixed heating circuit supply line (3)<br/>Assembly does NOT include a pump compensator – PAS L180 (Part No.: 001 338)<br/>Assembly does not include a pump<br/>Model DN 25 – Manifold assembly for manifold connection from the LEFT, PN 10 bar, Tmax 120°C
Generator circuit (NT): Kvs = 10.4 • V'max[250mbar] = 5.2m³/h • Q'max[20K] = 121kW • Q'max[10K] = 60kW • Leakage rate < 0.1%