rMIX DN25 2x4 LH-a

Item no. 001 160 Return flow utilisation
For highly efficient use of the return flow of an unmixed high-temperature circuit in a mixed low-temperature circuit at a condensing boiler, a stratified tank or a heat transfer station.

Recommended accessories

								

DÜV DN15 2x2 MUL set L

001344

Further information?

Further questions?

Contact technical support
					

Configure product variant

Nominal width

DN25

Performance class

Direct heating circuit (HT):
Kvs = 6.2 • V'max[100mbar] = 2m³/h
Q'max[20K] = 47kW
Mixing circuit (LT):
Kvs = 6.2 • V'max[100mbar] = 2m³/h
Q'max[10K] = 23kW

Flow direction producer

Flow direction Producer Left

Product documentation

Assembly instructions

Assembly instructions: For specialist partners only.
Please log in here or register here

Actuator multi-way mixer: For specialist partners only.
Please log in here or register here

Spare parts drawing

Spare parts drawing For specialist partners only.
Please log in here or register here

Data sheet

001160_DBL_2019-12-10.pdf

Tender text

Baunach article master data Version: 22.11.23

BAFA funding opportunity within the scope of heating system optimisation by replacing heating circulating pumps with high-efficiency circulating pumps.

rendeMIX multi-port mixing manifold with 3/3-way tangential mixing valve DN25×G1½(a) MsGuss (red adapter), plug and cover Ms58

For highly efficient use of the return flow of an unmixed high-temperature circuit in a mixed low-temperature circuit at a condensing boiler, a stratified tank or a heat transfer station.

Actuator EMS 240, 230V~ 50Hz 3.5VA 3-point signal, 5Nm (240h), 240°, 93s

Dual circuit manifold assembly with 2 connections to the heat source and 4 connections to the heat sinks, CuØ35×1, DN32×G1½(a) flat, pipe spacing 100mm.

2 integrated gravity brakes/backflow preventer, Dp10mbar

Direct heating circuit (HT): Kvs = 6.2 - V'max[100mbar] = 2m³/h - Q'max[20K] = 47kW - Mixed heating circuit (LT): Kvs = 6.2 - V'max[100mbar] = 2m³/h - Q'max[10K] = 23kW - Leakage rate < 0,1%

6 Thermometers 0-120°C, Ø63mm, soldering sleeves Ms58

6 ball valve unions, DN25 passage, PN32, G1½(i)×Rp1 flat-sealing, stuffing box, sealing hole, spindle with aluminium wing handle

Insulating moulded tray EPP 40g/l, black, 450×450mm, quick assembly kit

Without pump flanges

Assembly does NOT include pump compensator - PAS L180 (Part No.: 001 338)

With built-in high-efficiency Grundfos UPM3 pump, DN25, 130mm, H 5-6mWS, 230V~ 50Hz, 2m connection cable, EEI < 0,2

Model DN 25 - light version, PN 10bar, Tmax 120°C

Performance data

Direct heating circuit (HT): Kvs = 6.2 - V'max[100mbar] = 2m³/h - Q'max[20K] = 47kW - Mixed heating circuit (LT): Kvs = 6.2 - V'max[100mbar] = 2m³/h - Q'max[10K] = 23kW - Leakage rate < 0,1%