For connecting ONE ADDITIONAL servomotor to a controller output with a 230V~ 3-point signal. Multiple isolating relays can be connected in series—allowing an ADDITIONAL servomotor to be connected to the controller signal in each case.
BAFA Funding Opportunity for Heating System Optimization Through Hydraulic Balancing and Installation of Separate Control Technology
Electrical Isolation Relay +1
For connecting ONE ADDITIONAL actuator to a controller output with a 3-point signal at 230 V AC. Multiple isolation relays can be connected in series—allowing an ADDITIONAL actuator to be connected to the controller signal in each case.
Terminals U1: NOT USED
Terminals U2: Pass-through signals from the controller to the first motor (230 V AC) OPEN | CLOSED | L | N
Terminals U3: Signals to the additional actuator (230V~) OPEN | CLOSED | NTerminals U4: Pass-through signals from the controller to the first actuator (230V~) OPEN | CLOSED | L | NTerminals PE: Ground or protective conductor (NOT required for rendeMIX actuators—Protection Class II)Rated voltage of relay contacts: max. 250 V AC, max. 3 APower supply fuse rating: max. 6 ARelay current consumption: 10 mAOperating temperature: -10..+50°C, storage temperature: -30..+80°CLIFE-THREATENING DANGER: Connection must be performed only by a qualified electrician! Operation is permitted only in the supplied IP54-rated, insulated enclosure!