Accessories
For actuators with 70s running time (e.g. EMS 90 3P)
BAFA Funding Opportunity for Heating System Optimization Through Hydraulic Balancing and Installation of Separate Control TechnologyElectrical Signal Converter 0-10V -> 3-Point Signal 230V AC
For actuators with a 70-second runtime (e.g., EMS 90 3P)Terminal 01: Actuator CLOSEDTerminal 02: Actuator OPENTerminal 03: Actuator supply voltageLoad on the normally open contacts: max. 250 V AC, max. 6 ATerminals 04/05: Input signal 0–10 V (Ri: 1 MΩ)Terminals 10/11: Supply voltage 10..40 V DC or 9..30 V AC
Power consumption: max. 1 W
Operating temperature: -10..+50°C, storage temperature: -30..+80°CTS35 snap-on plastic enclosure per EN50022 (top-hat rail)Dimensions: 24×72×94 mm (W×H×D), Weight: 106 g------------------------------------------------------------------------Ordering information: Fixed factory setting, Input 1 = 0..10V, runtime = 70s